Home / Tools / Creepage and clearance calculator

Creepage and clearance calculator

Creepage and clearance, in three answers

For transformers and inductors from 50 Hz to 10 MHz. Say what the part goes into, the voltage across the insulation and the kind of insulation, and you get the two minimum distances with the standard they come from.

01

What does it go into?

Application sector

The standard is picked for you.

02

What voltage does the insulation see?

V

The highest voltage that sits across this insulation in normal service. Above 30 kHz the high frequency rules of the standard apply, and distances grow.

03

What kind of insulation?

Insulation

Environment

Insulating material

If the datasheet of the bobbin or the board does not state a CTI, leave group IIIb. It is the conservative choice.

More conditions
V
V
m

Leave the peak empty for a sinusoidal or DC voltage. Fill it in for a switched waveform whose peak is higher than the RMS value suggests.

Free to use. No sign-up for the first calculations of the day.

The method

How the calculator works

Creepage and clearance are the two minimum distances that keep insulation safe. The calculator takes the application sector to pick the standard, the working voltage and its frequency, the kind of insulation, the pollution degree and the material group, and returns both distances with the clause they come from.

Creepage and clearance, the difference

Clearance is the shortest distance through air between two conductive parts. It protects against flashover and is set mainly by the peak voltage, including transients. Creepage is the shortest distance along the surface of the insulation. It protects against tracking and is set by the working voltage, the pollution degree and the material group.

What moves the result

  • Working voltage. Higher voltage means larger distances, for both creepage and clearance.
  • Frequency. Above 30 kHz the high frequency rules of the standard apply, and the distances grow.
  • Kind of insulation. Reinforced or double insulation needs larger distances than basic insulation.
  • Pollution degree. A sealed or potted part (PD1) needs less creepage than a part exposed to dust or moisture (PD3).
  • Material group. Materials with a higher comparative tracking index (CTI) allow shorter creepage distances.
  • Altitude. Above 2,000 m, clearances are increased by a correction factor.

A worked example

A transformer for a power converter sees 400 V AC across its primary to secondary insulation, inside an indoor enclosure. With reinforced insulation, pollution degree 2 and a bobbin material of unknown CTI, the calculator returns a minimum creepage of 8 mm and a minimum clearance of 4 mm, under IEC 62477-1 (IEC 60664-1 Tables 10/11). Switching the bobbin to a group I material reduces the creepage to 4 mm.

Typical distances at a glance

Minimum distances for a power converter magnetic at 50 Hz, indoor electronics (pollution degree 2) and a material of unknown CTI (group IIIb). Use the calculator above for your exact conditions, frequency and material.

Typical minimum creepage and clearance distances for a power converter magnetic
Working voltageInsulationMinimum creepage (mm)Minimum clearance (mm)Standard and clause
230 V ACBasic2.51.5IEC 62477-1 (IEC 60664-1 Tables 10/11)
230 V ACReinforced5.02.0IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6)
400 V ACBasic4.03.0IEC 62477-1 (IEC 60664-1 Tables 10/11)
400 V ACReinforced8.04.0IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6)
690 V ACBasic8.05.5IEC 62477-1 (IEC 60664-1 Tables 10/11)
690 V ACReinforced16.08.0IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6)
800 V DCBasic8.05.5IEC 62477-1 (IEC 60664-1 Tables 10/11)
800 V DCReinforced16.08.0IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6)
1000 V DCBasic10.05.5IEC 62477-1 (IEC 60664-1 Tables 10/11)
1000 V DCReinforced20.08.0IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6)

Values calculated with this tool. Always check them against the edition of the standard your product is certified to.

After the number

The distance is fixed. The volume it costs is not.

Creepage can be folded into a bobbin flange, a barrier or a potted interface instead of being laid out flat, and that is most of the difference between a transformer that meets the standard and one that also fits. If the distances above do not fit your envelope, send us the specification and we will look at how to get them in.

Send us your spec

Straight answers

Creepage and clearance, the usual questions.

What is the difference between creepage and clearance?
Clearance is the shortest path through air between two conductors. Creepage is the shortest path along the surface of the insulation between them. A design has to meet both, and the larger requirement usually sets the size of the part.
Why do the distances grow above 30 kHz?
At high frequency the electric field stresses insulation differently, and the standards apply specific rules above 30 kHz that require larger distances. The calculator applies them automatically when you enter the frequency.
Which pollution degree should I choose?
Pollution degree 1 applies to sealed or potted parts, 2 to most indoor electronics, 3 to industrial, dusty or damp environments, and 4 to outdoor exposed equipment. When in doubt, pick the higher one.
What if I do not know the CTI of my bobbin or board material?
Choose group IIIb. It is the most conservative option and gives the largest creepage, so the result stays safe until you confirm the material data.
How much larger is reinforced insulation?
In most standards the creepage for reinforced insulation is twice the value for basic insulation, and the clearance is also higher. The calculator applies the factor that the selected standard requires.
Can you design the insulation system of my transformer?
Yes. Creepage and clearance are one input to the design. We also choose the bobbin, margin tape, triple insulated wire or potting that meets them in the smallest volume. Send us your specification.