Home / Tools / Creepage and clearance calculator
Creepage and clearance calculator
Creepage and clearance, in three answers
For transformers and inductors from 50 Hz to 10 MHz. Say what the part goes into, the voltage across the insulation and the kind of insulation, and you get the two minimum distances with the standard they come from.
The method
How the calculator works
Creepage and clearance are the two minimum distances that keep insulation safe. The calculator takes the application sector to pick the standard, the working voltage and its frequency, the kind of insulation, the pollution degree and the material group, and returns both distances with the clause they come from.
Creepage and clearance, the difference
Clearance is the shortest distance through air between two conductive parts. It protects against flashover and is set mainly by the peak voltage, including transients. Creepage is the shortest distance along the surface of the insulation. It protects against tracking and is set by the working voltage, the pollution degree and the material group.
What moves the result
- Working voltage. Higher voltage means larger distances, for both creepage and clearance.
- Frequency. Above 30 kHz the high frequency rules of the standard apply, and the distances grow.
- Kind of insulation. Reinforced or double insulation needs larger distances than basic insulation.
- Pollution degree. A sealed or potted part (PD1) needs less creepage than a part exposed to dust or moisture (PD3).
- Material group. Materials with a higher comparative tracking index (CTI) allow shorter creepage distances.
- Altitude. Above 2,000 m, clearances are increased by a correction factor.
A worked example
A transformer for a power converter sees 400 V AC across its primary to secondary insulation, inside an indoor enclosure. With reinforced insulation, pollution degree 2 and a bobbin material of unknown CTI, the calculator returns a minimum creepage of 8 mm and a minimum clearance of 4 mm, under IEC 62477-1 (IEC 60664-1 Tables 10/11). Switching the bobbin to a group I material reduces the creepage to 4 mm.
Typical distances at a glance
Minimum distances for a power converter magnetic at 50 Hz, indoor electronics (pollution degree 2) and a material of unknown CTI (group IIIb). Use the calculator above for your exact conditions, frequency and material.
| Working voltage | Insulation | Minimum creepage (mm) | Minimum clearance (mm) | Standard and clause |
|---|---|---|---|---|
| 230 V AC | Basic | 2.5 | 1.5 | IEC 62477-1 (IEC 60664-1 Tables 10/11) |
| 230 V AC | Reinforced | 5.0 | 2.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6) |
| 400 V AC | Basic | 4.0 | 3.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11) |
| 400 V AC | Reinforced | 8.0 | 4.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6) |
| 690 V AC | Basic | 8.0 | 5.5 | IEC 62477-1 (IEC 60664-1 Tables 10/11) |
| 690 V AC | Reinforced | 16.0 | 8.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6) |
| 800 V DC | Basic | 8.0 | 5.5 | IEC 62477-1 (IEC 60664-1 Tables 10/11) |
| 800 V DC | Reinforced | 16.0 | 8.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6) |
| 1000 V DC | Basic | 10.0 | 5.5 | IEC 62477-1 (IEC 60664-1 Tables 10/11) |
| 1000 V DC | Reinforced | 20.0 | 8.0 | IEC 62477-1 (IEC 60664-1 Tables 10/11; reinforced per 5.1.6) |
Values calculated with this tool. Always check them against the edition of the standard your product is certified to.
After the number
The distance is fixed. The volume it costs is not.
Creepage can be folded into a bobbin flange, a barrier or a potted interface instead of being laid out flat, and that is most of the difference between a transformer that meets the standard and one that also fits. If the distances above do not fit your envelope, send us the specification and we will look at how to get them in.
Find a standard part with the same values in our component finder.
Straight answers